Performance Requirement · NCC 2025 Volume Three

B3P6 Pressure

Part B3 Non-drinking water services · NCC 2019: BP3.3

Open B3P6 on NCC Online ↗

The points of discharge for a non-drinking water service must—

have—

a working pressure of not less than 50 kPa; and

a static pressure within the building of not more than 500 kPa: or

have water pressures suitable for the correct functioning of the fixture or appliance where water pressures outside of (a)(i) and (a)(ii) are required.

Changed since NCC 2022. See NCC 2022 Volume Three B3P6, or show what changed.

A The points of discharge for a non-drinking water service must avoid failure — have — a working pressure of not less than 50 kPa; and a static pressure within the building of not more than 500 kPa: or uncontrolled discharge. have water pressures suitable for the correct functioning of the fixture or appliance where water pressures outside of (a)(i) and (a)(ii) are required.

Removed words are struck through; added words are highlighted. Comparison of the text only.