Performance Requirement · NCC 2025 Volume Three

B3P7 Uncontrolled discharge

Part B3 Non-drinking water services

Open B3P7 on NCC Online ↗

Any failure or uncontrolled discharge from a non-drinking water service must be avoided.

Changed since NCC 2022. See NCC 2022 Volume Three B3P7, or show what changed.

A Any failure or uncontrolled discharge from a non-drinking water service must ensure the efficient use of non-drinking water by — limiting water usage from — a cistern or flushing device for a urinal, to a flush volume of not more than 2.5 litres for each — single urinal stall; or 600mm length of a continuous urinal wall; and a dual flush cistern or flushing valve that is connected to a water closet pan, to a flush volume of not more than — 6 and 3 litres; or 4.5 and 3 litres; or water saving measures equivalent to or greater than those described in (a). Applications The flush volumes of B3P7 may be within a tolerance of — ±0.5 litres for the full flush of a 6/3 litre cistern; or ±0.5 litres for the reduced flush of a 6/3 litre cistern; or ±0.2 litres for a 4.5/3 litre cistern. Exemptions The requirements of B3P7 do not apply to a vacuum drainage system. avoided.

Removed words are struck through; added words are highlighted. Comparison of the text only.