B5D2 Drinking water service
Part B5 Cross-connection control · NCC 2019: B5.2
(1) A hazard exists wherever it is possible for water or contaminants to enter a drinking water service or supply via any potential or actual cross-connection between—
the drinking water service; and
any of the following:
A non-drinking water service.
A rainwater service.
An alternative water supply.
A swimming pool.
Pipes, fixtures or specialist equipment (including boilers and pumps) containing chemicals, liquids, gases or other substances which may be harmful to health or safety.
(2) Each hazard must—
be assigned—
an Individual protection Hazard Rating in accordance with B5D7(4), (5),or (6); or
a zone protection hazard rating in accordance with B5D7(7), (8), (9); and
be isolated from the drinking water service by an appropriate backflow prevention device which is selected and installed in accordance with AS/NZS 3500.1.
(3) Where a site is served by a Network Utility Operator’s drinking water supply, appropriate containment protection must be selected and installed in accordance with of AS/NZS 3500.1.
Changed since NCC 2022. See NCC 2022 Volume Three B5D2, or show what changed.
(1) A hazard exists wherever it is possible for water or contaminants to enter a drinking water service or supply via any potential or actual cross-connection between — the drinking water service; and any of … health or safety. (2) Each hazard must — be assigned — an Individual protection Hazard Rating or Zone protection Hazard Rating in accordance with S41C4 and S41C5 ; B5D7(4), (5),or (6); or a zone protection hazard rating in accordance with B5D7(7), (8), (9); and be isolated from the drinking water service by an appropriate backflow prevention device which is selected and installed in accordance with Section 4 of AS/NZS 3500.1. (3) Where a site is served by a … containment protection must be selected and installed in accordance with Section 4 of AS/NZS 3500.1.