Performance Requirement · NCC 2025 Volume Three

C1P3 Water efficiency

Part C1 Sanitary plumbing systems · NCC 2019: CP1.1

Open C1P3 on NCC Online ↗

A sanitary plumbing system must ensure efficient use of drinking water by—

limiting water usage from—

a cistern or flushing device for a urinal, to a flush volume of not more than 2.5 litres for each—

single urinal stall; or

600 mm length of a continuous urinal wall; and

a dual flush cistern or flushing valve that is connected to a water closet pan to a flush volume of not more than—

6 and 3 litres; or

4.5 and 3 litres; or

water saving measures equivalent to or greater than those described in (a).

Applications

The flush volume of C1P3 may be within a tolerance of—

±0.5 litres for the full flush of a 6/3 litre cistern; or

+0.5 litres for the reduced flush of a 6/3 litre cistern; or

±0.2 litres for a 4.5/3 litre cistern.

Exemptions

The requirements of C1P3 do not apply to a vacuum drainage system.

Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three C1P3.