NCC 2025 Volume Three
Part C1 Sanitary plumbing systems
18 clauses · Open on NCC Online ↗
- C1O1 ObjectiveThe Objective of this Part is to— safeguard people from illness, injury or loss (including loss of amenity) due to the failure of a sanitary…
- C1F1 Disposal systemSanitary fixtures and sanitary appliances must be provided with an adequate disposal system that does not impact adversely on the occupants of the…
- C1P1 DisposalSewage and sullage must be conveyed through a sanitary plumbing system to— a sanitary drainage system; or an approved disposal system authorised by…
- C1P2 AccessAccess must be provided to components of a sanitary plumbing system that require maintenance or replacement including mechanical devices, controls…
- C1P3 Water efficiencyA sanitary plumbing system must ensure efficient use of drinking water by— limiting water usage from— a cistern or flushing device for a urinal, to…
- C1P4 Uncontrolled dischargeAny failure or uncontrolled discharge from a sanitary plumbing system must be avoided.
- C1P5 VentilationA sanitary plumbing system must ensure that ventilation is provided to avoid hydraulic load imbalance such that— there is less than a 1% likelihood…
- C1P6 ContaminationThe entry of water, foul gases, sewerage and sullage from a sanitary plumbing system into buildings must be avoided. (2) The entry of foul gases…
- C1P7 DamageDamage to a sanitary plumbing system from superimposed loads, ground movement or root penetration must be avoided.
- Table C1V1a Frequency factorsNCC building class | NCC building class example | Frequency factor (K) | Time interval between fixture use averaged over peak period (s) Class 1 |…
- Table C1V1b Discharge unitsFixture | Discharge Units (DU) Basin | 0.3 Bath (with shower) | 0.5 Bath (without shower) | 0.6 Bidet | 0.3 Shower (single) | 0.4 Urinal (wall-hung)…
- C1V1 Determination of sanitary plumbing wastewater flowratesCompliance with C1P3 for pipe sizing is verified for each sanitary plumbing pipework section when the discharge flowrate is not less than the…
- C1V2 System design using wastewater flowratesCompliance with C1P5 for pipe sizing is verified for the plumbing design when— fully vented systems and fully vented modified systems are designed…
- C1D1 Deemed-to-Satisfy ProvisionsWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirement C1P1 to C1P7 is satisfied by complying with C1D2 to C1D5. (2) Where a…
- C1D2 Invert levelsThe invert level of a trap or gully weir must be a minimum of 10 mm higher than the soffit of the pipe to which it connects.
- C1D3 General requirements SA WAA sanitary plumbing system must be in accordance with AS/NZS 3500.2.
- C1D4 Bushfire prone areasA sanitary plumbing system in a designated bushfire prone area must be in accordance with AS 3959.
- C1D5 Water efficiencyA sanitary plumbing system must ensure the efficient use of drinking water by— limiting water usage from— a cistern or flushing device for a urinal,…