Verification Method · NCC 2025 Volume Three

C2V4 Sanitary drainage design

Part C2 Sanitary drainage systems

Open C2V4 on NCC Online ↗

(1) Compliance with C2P1 for main drains and branch drains is verified if (2) to (4) are complied with.

(2) Sanitary drainage pipework shall be sized in accordance with AS 2200 and C2V1.

(3) The following limitations shall be applied:

The size of the drain shall be of nominal size as specified in Table 3.4.1 of AS/NZS 3500.2.

The minimum size of a main drain shall be as per Clause 3.3.2 of AS/NZS 3500.2.

The minimum size of a branch drain shall be as per Clause 3.3.3 of AS/NZS 3500.2.

Not more than 2 water closet pans shall be connected to a vented DN 80 branch drain.

(4) When using the Colebrook-White equation provided in AS 2200—

minimum and maximum pipe grades shall be designed such that (2) is satisfied; and

the filling degree shall be designed such that (2) is satisfied; and

the flowrate of the designed drain must be greater than or equal to that determined in accordance with C2V3; and

unless alternative values are appropriate, the design values must be—

1.5 mm for pipe roughness; and

1.01 x 10-6 m2s-1 for kinematic viscosity.

New in NCC 2025. No C2V4 in NCC 2022 Volume Three; it may have moved or been renumbered.