C2V3 Determination of sanitary drainage wastewater flowrates
Part C2 Sanitary drainage systems
(1) Compliance with C2P1 for pipe sizing is verified for each sanitary drainage pipework section when the design flow rate is not less than—
the probable simultaneous wastewater flow rate calculated in accordance with (2); or
the Discharge Unit (DU) value of the highest fixture connected upstream of the pipework section as given by Table C2V3b, in litres per second, whichever is greater.
(2) For the purposes of (1)(a), for each pipework section, the design probable simultaneous wastewater flow rate must be calculated in accordance with the following:
[formula] (3) In the equation shown at (2):
[formula] = the probable simultaneous wastewater flowrate for that pipework section (l/s).
[formula] = the sum of any other wastewater flowrates such as pumped discharges (l/s).
[formula] = the frequency factor given in Table C2V3a (dimensionless).
[formula] = the sum of the discharge units as given in Table C2V3b connected upstream of that pipework section (dimensionless).
Table C2V3a Frequency factors
NCC building class
NCC building class example
Frequency factor (K)
Time interval between fixture use averaged over peak period (s)
Class 1
Residential dwelling, duplexes, or townhouses
0.5
1200
Class 2
Apartment or unit
0.5 - 0.8
450 - 1200
Class 3
Hotel, hostel, dormitory
0.6 - 0.8
450 - 800
Class 4
Sole dwelling within a Class 5-9 building
0.5
1200
Class 5
Office
0.6 - 0.8
450 - 800
Class 6
Retail, shop, restaurant, café
0.6 - 0.8
450 - 800
Class 7
Carpark, warehouse, storage building
0.6 - 0.8
450 - 800
Class 8
Factory, workshop, laboratory
0.6 - 0.8
450 - 800
Class 9a
Healthcare building, hospital, and GP clinics
0.6 - 0.8
450 - 800
Class 9b
Public event buildings, stadiums, theatres, schools, universities, and churches
1.0 - 1.2
200 - 300
Class 9c
Aged care facilities
0.6 - 0.8
450 - 800
Table C2V3b Discharge units
Fixture
Discharge Units (DU)
Basin
0.3
Bath (with shower)
0.5
Bath (without shower)
0.6
Bidet
0.3
Shower (single)
0.4
Urinal (wall-hung)
0.5
Urinal (stall for each 600 mm length of slab)
0.2
Kitchen sink
0.6
Water closet (6L cistern)
1.8
Water closet (4L cistern)
1.8
Washing machine
0.6
Domestic dishwasher
0.6
Floor waster gully
Sum of DU from connected fixtures
Notes
In applying Table C2V3b, the practitioner may introduce their own fixture values where a desired fixture type is not listed.
Tables
Changed since NCC 2022. See NCC 2022 Volume Three C2V3, or show what changed.
(1) Compliance with C2P1 for pipe sizing is verified for … upstream of that pipework section (dimensionless). Table C2V3a Frequency factors Fixture usage NCC building class NCC building class example Frequency factor (K) Intermittent Time interval between fixture use e.g. averaged over peak period (s) Class 1 Residential dwelling, guesthouse duplexes, or office townhouses 0.5 1200 Class 1, Class 2, 2 Apartment or unit 0.5 - 0.8 450 - 1200 Class 3 or Hotel, hostel, dormitory 0.6 - 0.8 450 - 800 Class 4 Sole dwelling within a Class 5-9 building 0.5 Frequent use e.g. hospital, restaurant or hotel 1200 Class 5, 5 Office 0.6 - 0.8 450 - 800 Class 6, 6 Retail, shop, restaurant, café 0.6 - 0.8 450 - 800 Class 7, 7 Carpark, warehouse, storage building 0.6 - 0.8 450 - 800 Class 8, 8 Factory, workshop, laboratory 0.6 - 0.8 450 - 800 Class 9a or Healthcare building, hospital, and GP clinics 0.6 - 0.8 450 - 800 Class 9b Public event buildings, stadiums, theatres, schools, universities, and churches 1.0 - 1.2 200 - 300 Class 9c 0.7 Congested use e.g. open to the general public, school Class 9b 1.0 Special use e.g. laboratory Not applicable 1.2 Aged care facilities 0.6 - 0.8 450 - 800 Table C2V3b Discharge units Fixture System 1 - Discharge Units (DU) System 2 - Discharge Units (DU) System 3 - Discharge Units (DU) Basin 0.3 Bath (with shower) 0.5 0.3 Bath (without shower) 0.6 Bidet 0.3 Shower 0.6 0.4 (single) 0.4 Urinal 0.8 (wall-hung) 0.5 0.4 Bath 0.8 0.6 1.3 Urinal (stall for each 600 mm length of slab) 0.2 Kitchen sink 0.8 0.6 1.3 Water closet 2.0 (6L cistern) 1.8 1.2 Water closet (4L cistern) 1.8 Washing machine - Up to 6 kg 0.8 0.6 0.6 Domestic dishwasher 0.8 0.6 0.2 Floor waster gully Sum of DU from connected fixtures Notes In applying Table C2V3b, the practitioner may introduce their own fixture values where a desired fixture type is not listed.