New South Wales variation · NCC 2025 Volume Three

NSW B1D2 Water Efficiency

NSW Part B1 Cold water services · varies B1D2 Water efficiency

Open on NCC Online ↗

Delete clause B1D2 and insert NSW B1D2 as follows:

(1) A tap or outlet used for a shower, basin, kitchen sink or laundry trough must be a minimum of 3 Star WELS rated and discharge not more than 9 litre per minute.

(2) Cisterns or flushing devices for water closets must—

Have a dual flushing mechanism; and

Be a minimum 3 Star WELS rating discharging not more than 6 litres or 4.5 litre for a full flush.

(3) Cisterns or flushing devices for urinals must—

Be a minimum 2 Star WELS rating discharging a volume of not more than 2.5 litres of each—

Single urinal stall; or

600mm length of continuous urinal wall; and

Not be set-cycled or activated by any method other than manual or use activation.

Applications

B1D2(1) applies to outlets that provide cold water only. The Deemed-to-Satisfy Provision for outlets that deliver a combination of cold water and heated water is B2D4.

The flush volumes of B1D2(2) and B1D2(3) may be within a tolerance of—

±0.5 litres for the full flush of a 6/3 litre cistern; or

+0.5 litres for the reduced flush of a 6/3 litre cistern; or

±0.2 litres for a 4.5/3 litre cistern.

Exemptions

The requirements of B1D2(1) do not apply to a shower intended to provide rapid drenching of a person for emergency purposes, such as chemical removal.

The requirements of B1D2(2) and B1D2(3) do not apply to a vacuum drainage system.

The requirements of B1D2(3)(b) do not apply to a programmed solenoid operated flushing system if programmed to shut down during extended periods of non-occupancy of a building.

New in NCC 2025. No NSW B1D2 in NCC 2022 Volume Three; it may have moved or been renumbered.

The national clause

Other states and territories