NSW B3D3 General requirements
NSW Part B3 Non-drinking water services · varies B3D3 General requirements
Delete clause B3D3 and insert NSW B3D3 as follows:
A non-drinking water service must be in accordance with AS/NZS 3500.1, with the following additions to clause 10.3—
Clause 10.3(d): Top up from a drinking water supply shall be by an indirect trickle top up with a visible air gap external to the tank.
10.3(e): There shall be no connection between treated greywater systems and drinking water, rainwater or other sources of supply.
Changed since NCC 2022. See NCC 2022 Volume Three NSW B3D3, or show what changed.
Delete clause B3D3 and insert NSW B3D3 as follows: A non-drinking water service must be in accordance with AS/NZS 3500.1 3500.1, with the following additions to clause 10.3 — Clause 10.3(d): Top up from a drinking water supply shall be by an indirect trickle top up with a visible air gap external to the tank; and tank. 10.3(e): There shall be no connection between treated greywater systems and drinking water, rainwater or other sources of supply.
Removed words are struck through; added words are highlighted. Comparison of the text only.