Tasmania variation · NCC 2025 Volume Three

TAS B2D2 Water heater in a heated water supply system

TAS Part B2 Heated water services · varies B2D2 Water heater in a heated water supply system

Open on NCC Online ↗

Delete clause B2D2 and insert TAS B2D2 as follows:

In a new Class 1 or Class 10 building—

a water heater in a heated water supply system must be—

a solar water heater complying with (b); or

a heat pump water heater complying with (b); or

a gas water heater complying with (c); or

an electric resistance water heater complying with AS/NZS 3500.4; or

a wood fired thermosiphon water heater or direct fired water heater each complying with AS/NZS 3500.4; and

a solar water heater and a heat pump water heater must have—

for a building with 1 or 2 bedrooms—

at least 14 Small-scale Technology Certificates for the zone where it is being installed; or

an energy saving of not less than 40% in accordance with AS/NZS 4234 for a "small" load system; and

for a building with 3 or 4 bedrooms—

at least 22 Small-scale Technology Certificates for the zone where it is being installed; or

an energy saving of not less than 60% in accordance with AS/NZS 4234 for a "medium" load system; and

for a building with more than 4 bedrooms—

at least 28 Small-scale Technology Certificates for the zone where it is being installed; or

an energy saving of not less than 60% in accordance with AS/NZS 4234 for a “large” load system; and

a gas water heater must be rated not less than 5 stars in accordance with AS 4552.