Tasmania variation · NCC 2025 Volume Three
TAS B2P10 Pressure
TAS Part B2 Heated water services · varies B2P10 Pressure
Delete clause B2P10 and insert TAS B2P10 as follows:
(1) The points of discharge for a heated water service must—
have—
a working pressure of not less than 50 kPa; and
a static pressure within the building of not more than 500 kPa; or
have water pressures suitable for the correct functioning of the fixture or appliance where water pressures outside of (a)(i) and (a)(ii) are required.
Exemptions
B2P9(a)(i) and B2P9(a)(ii) do not apply to existing low-pressure gravity only water services.
New in NCC 2025. No TAS B2P10 in NCC 2022 Volume Three; it may have moved or been renumbered.