B2P10 Pressure
Part B2 Heated water services · NCC 2019: BP2.3
The points of discharge for a heated water service must—
have—
a working pressure of not less than 50 kPa; and
a static pressure within the building of not more than 500 kPa; or
have water pressures suitable for the correct functioning of the fixture or appliance where water pressures are outside of (a)(i) and (a)(ii) are required.
Changed since NCC 2022. See NCC 2022 Volume Three B2P10, or show what changed.
A The points of discharge for a heated water service must avoid failure — have — a working pressure of not less than 50 kPa; and a static pressure within the building of not more than 500 kPa; or uncontrolled discharge. have water pressures suitable for the correct functioning of the fixture or appliance where water pressures are outside of (a)(i) and (a)(ii) are required.