WA B2D5 Maximum delivery temperature
WA Part B2 Heated water services · varies B2D5 Maximum delivery temperature
Delete clause B2D5 and insert WA B2D5 as follows:
(1) The delivery temperature of heated water at the outlet of each sanitary fixture for a new heated water installation, or for an existing heated water installation if the requirements in this clause applied to the installation when it was a new installation, must be—
not more than 45°C in any—
residential part of an aged care building; or
patient care area in a health-care building; or
part of an early childhood centre, or primary or secondary school, that is used by children; or
designated accessible facility in a common area of a Class 2 building, or in any part of a Class 3, or Class 5 to Class 10 building; or
not more than 50°C in all other cases.
(2) The delivery temperature of heated water at the outlet of each sanitary fixture (other than a basin in a Class 1, 2, 4, 5, 6, 7, 8 or 10 building) for an existing heated water installation must meet the requirements for a new heated water installation if—
in relation to a heated water installation with multiple water heaters — all water heaters in the installation are replaced or relocated; or
in any other case — a water heater in the installation is replaced or relocated or an additional water heater is added to the installation.
Applications
B2D5 applies to heated water installations intended for personal hygiene as stated in the clause.