New South Wales variation · NCC 2025 Volume Three
NSW B2D5 Maximum delivery temperature
NSW Part B2 Heated water services · varies B2D5 Maximum delivery temperature
Delete clause B2D5 and insert NSW B2D5 as follows:
The delivery temperature of heated water at the outlet of each sanitary fixture must be—
not more than 45°C in any—
residential part of an aged care building; or
patient care area in a health-care building; or
part of an early childhood centre, or primary or secondary school, that is used by children; or
any facility designated for use by people with a disability; or
not more than 50°C in all other cases.
Applications
B2D5 applies to all heated water installations for personal hygiene purposes.
Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three NSW B2D5.