Deemed-to-Satisfy Provision · NCC 2025 Volume Three

B2D5 Maximum delivery temperature

Part B2 Heated water services · NCC 2019: B2.5, NSW B2.5(a)(iv)

Open B2D5 on NCC Online ↗
Varied in NSW, SA, WA. Check the variation for your state.

The delivery temperature of heated water at the outlet of each sanitary fixture must be—

not more than 45 °C in any—

residential part of an aged care building; or

patient care area in a health-care building; or

part of an early childhood centre, or primary or secondary school, that is used by children; or

designated accessible facility in a common area of a Class 2 building, or in any part of a Class 3 or Class 5 to Class 10 building; or

not more than 50 °C in all other cases.

Applications

B2D5 applies to all heated water installations intended for personal hygiene.

Changed since NCC 2022. See NCC 2022 Volume Three B2D5, or show what changed.

The delivery temperature of heated water at the outlet of … Class 2 building, or in any part of a Class 3, 3 or Class 5, Class 6, Class 7, Class 8, Class 9a, Class 9b, Class 9c or 5 to Class 10 building; or not more than 50 °C in … applies to all heated water installations intended for personal hygiene.

Removed words are struck through; added words are highlighted. Comparison of the text only.

State and territory variations all clauses side by side →