Verification Method · NCC 2025 Volume Two
H3V2 Avoidance of spread of fire from allotment boundary
Part H3 Fire safety · NCC 2019: V2.3.1.2
Compliance with H3P1(1)(b) to avoid the spread of fire from an allotment boundary is verified when—
the external walls and any openings in the external walls of a building, less than 0.9 m from an allotment boundary, are capable of withstanding 92.6 kW/m2 of heat flux for 60 minutes; and
the external walls extend to the underside of a non-combustible roof covering or non-combustible eaves lining in accordance with clause 9.2.3 of the ABCB Housing Provisions.
Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two H3V2.