Performance Requirement · NCC 2025 Volume Two

H3P1 Spread of fire

Part H3 Fire safety · NCC 2019: P2.3.1

Open H3P1 on NCC Online ↗
Varied in SA. Check the variation for your state.

(1) A Class 1 building must be protected from the spread of fire such that the probability of a building not being able to withstand the design heat flux of 92.6 kW/m² for a period of 60 minutes shall not exceed 0.01, when located within 900 mm from the allotment boundary or within 1.8 m from another building on the same allotment from—

another building other than an associated Class 10 building; and

the allotment boundary, other than a boundary adjoining a road or public space (see Figure H3P1).

(2) A Class 10a building must not significantly increase the risk of fire spread between Class 2 to 9 buildings.

Figure H3P1 Typical areas of potential fire spread

Figure Notes

This diagram indicates areas of potential fire spread. This situation will differ for corner allotments, etc.

Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two H3P1.