H3V3 Avoidance of spread of fire between buildings on adjoining allotments
Part H3 Fire safety · NCC 2019: V2.3.1.3
Compliance with H3P1(2) to avoid the spread of fire between buildings on adjoining allotments is verified when it is calculated that—
a building will not cause heat flux in excess of those set out in column 2 of Table H3V3 at locations within the boundaries of an adjoining property set out in column 1 of Table H3V3 where another building may be constructed; and
when located at the distances from the allotment boundary set out in column 1 of Table H3V3, a building is capable of withstanding the heat flux set out in column 2 of Table H3V3 without ignition.
Table H3V3 Heat flux (adjoining allotment)
Column 1 (Location)
Column 2 (Heat flux [kW/m2])
On boundary
80
1 m from boundary
40
3 m from boundary
20
6 m from boundary
10