Verification Method · NCC 2025 Volume Two

H7V2 Buildings in bushfire prone areas

Part H7 Ancillary provisions and additional construction requirements · NCC 2019: V2.7.2

Open H7V2 on NCC Online ↗

(1) Compliance with H7P5 is verified if the ignition probability for a building exposed to a design bushfire does not exceed 10%.

(2) Bushfire design actions must be determined in consideration of the annual probability of a design bushfire derived from—

assigning the building or structure an Importance Level in accordance with (3); and

determining the corresponding annual probability of exceedance in accordance with Table H7V2.

(3) A building or structure's Importance Level must be identified as one of the following:

Importance Level 1 — where the building or structure presents a low degree of hazard to life and other property in the case of failure.

Importance Level 2 — where the building or structure is not of Importance Level 1 or 4 and is a Class 1a or 1b building accommodating 12 people or less.

Importance Level 4 — where the building is a Class 10c building and is subject to a necessary ‘defend in place’ strategy.

(4) The ignition probability for a building must be assessed by application of the following:

An event tree analysis of relevant bushfire scenarios.

Design bushfire conditions that include combinations of the following actions appropriate to the distance between the building and the bushfire hazard:

Direct attack from airborne burning embers.

Burning debris and accumulated embers adjacent to a building element.

Radiant heat from a bushfire front.

Direct flame attack from a bushfire front.

(5) Applied fire actions must allow for reasonable variations in—

fire weather; and

vegetation, including fuel load, burning behaviour of vegetation (including the potential for crown fires); and

the distance of the building from vegetation; and

topography, including slopes and features that may shield; and

ignition of adjacent buildings, building elements, plants, mulch and other materials; and

effective size of fire front; and

duration of exposure; and

flame height; and

flame tilt; and

flame adhesion to sloping land; and

the height of the building and its elements.

(6) The assessment process must include consideration of—

the probability of non-complying construction of critical aspects of an approved design; and

the probability of critical aspects of an approved design being fully functional during the life of the building; and

inclusion of safety factors; and

sensitivity analysis of critical aspects of a proposed design.

Table H7V2 Annual Probability of Exceedance (APE) for design bushfire actions

Importance Level

Complex analysis APE for bushfire exposure

Simple analysis APE for weather conditions (design bushfire)

1

No requirement

No requirement

2

1:500

1:50

3

N/A for Class 1 and 10 buildings

N/A for Class 1 and 10 buildings

4

1:2000

1:200

Table Notes

Complex analysis must consider the probability of ignition, fire spread to the urban interface and penetration of the urban interface coincident with fire weather conditions.

Tables

Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two H7V2.

Clauses referred to

Defined terms used