SA H3P1 Spread of fire
SA Part H3 Fire safety · varies H3P1 Spread of fire
Delete subclause H3P1(1) and insert SA H3P1(1) as follows:
(1) A Class 1 building must be protected from the spread of fire such that the probability of a building not being able to withstand the design heat flux of 92.6 kW/m² for a period of 60 minutes shall not exceed 0.01, when located within 900 mm from the allotment boundary or within 1.8 m from another building on the same allotment from—
another building other than an associated Class 10 building; and
the allotment boundary, other than a boundary adjoining a road or public space (see Figure H3P1); and
a Class 10b brush fence.
Changed since NCC 2022. See NCC 2022 Volume Two SA H3P1, or show what changed.
Delete subclause H3P1(1) and insert SA H3P1(1) as follows: (1) A Class 1 building must be protected from the spread of fire such that the probability of a building not being able to withstand the design heat flux of 92.6 kW/m² for a period of 60 minutes shall not exceed 0.01, when located within 900 mm from the allotment boundary or within 1.8 m from another building on the same allotment from — another building other than an associated Class 10 building; and the allotment boundary, other than a boundary adjoining a road or public space; space (see Figure H3P1); and a Class 10b brush fence.
Removed words are struck through; added words are highlighted. Comparison of the text only.