Table · NCC 2025 Volume Two

Table S1C2f FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces filled

Specification 1 Fire-resistance of building elements

Open Table S1C2f on NCC Online ↗
Fire protectionMinimum thickness (mm) of principal material for FRLs
60/60/6090/90/90120/120/120180/180/180240/240/240
Solid calcium-silicate masonry5050505065
Solid clay masonry5050506590
Solid concrete masonry5050506590
Solid gypsum blocks5050505065
Hollow terracotta blocks — plastered 13 mm5050506590

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table for S1C2 Rating

Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two Table S1C2f.