Table · NCC 2025 Volume Two
Table S1C2f FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces filled
Specification 1 Fire-resistance of building elements
| Fire protection | Minimum thickness (mm) of principal material for FRLs | ||||
|---|---|---|---|---|---|
| 60/60/60 | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 | |
| Solid calcium-silicate masonry | 50 | 50 | 50 | 50 | 65 |
| Solid clay masonry | 50 | 50 | 50 | 65 | 90 |
| Solid concrete masonry | 50 | 50 | 50 | 65 | 90 |
| Solid gypsum blocks | 50 | 50 | 50 | 50 | 65 |
| Hollow terracotta blocks — plastered 13 mm | 50 | 50 | 50 | 65 | 90 |
Table Notes
For the purposes of this table, each element must meet the requirements of Specification 2.
Table for S1C2 Rating
Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two Table S1C2f.