Table · NCC 2025 Volume Two

Table S1C2g FRLs deemed to be achieved by hot-rolled steel columns (including a fabricated column) exposed on no more than 3 sides and with column spaces unfilled

Specification 1 Fire-resistance of building elements

Open Table S1C2g on NCC Online ↗
Fire protectionMinimum thickness (mm) of principal material for FRLs
60/60/6090/90/90120/120/120180/180/180240/240/240
Solid calcium-silicate masonry505050--
Solid clay masonry505065--
Solid concrete masonry505065--
Solid gypsum blocks505050--
Hollow terracotta blocks — plastered 13 mm505065--

Table Notes

For the purposes of this table, each element must meet the requirements of Specification 2.

Table for S1C2 Rating

Same wording in NCC 2022 Volume Two. See NCC 2022 Volume Two Table S1C2g.