C2D3 Calculation of rise in storeys
Part C2 Fire resistance and stability · NCC 2019: C1.2
(1) The rise in storeys is the sum of the greatest number of storeys at any part of the external walls of the building and any storeys within the roof space—
above the finished ground next to that part; or
if part of the external wall is on the boundary of the allotment, above the natural ground level at the relevant part of the boundary.
(2) A storey is not counted if—
it is situated at the top of the building and contains only heating, ventilating or lift equipment, water tanks, or similar service units or equipment; or
it is situated partly below the finished ground and the underside of the ceiling is not more than 1 m above the average finished level of the ground at the external wall, or if the external wall is more than 12 m long, the average for the 12 m part where the ground is lowest.
(3) In a Class 7 or 8 building, a storey that has an average internal height of more than 6 m is counted as—
one storey if it is the only storey above the ground; or
2 storeys in any other case.
(4) For the purposes of calculating the rise in storeys of a building—
a mezzanine is regarded as a storey in that part of the building in which it is situated if its floor area is more than 200 m2 or more than ⅓ of the floor area of the room, whichever is the lesser; and
two or more mezzanines are regarded as a storey in that part of the building in which they are situated if they are at or near the same level and have an aggregate floor area more than 200 m2 or more than ⅓ of the floor area of the room, whichever is the lesser.