Deemed-to-Satisfy Provision · NCC 2025 Volume One
C2D4 Buildings of multiple classification
Part C2 Fire resistance and stability · NCC 2019: C1.3
(1) In a building of multiple classifications, the Type of construction required for the building is the most fire-resisting Type resulting from the application of Table C2D2 on the basis that the classification applying to the top storey applies to all storeys.
(2) In a building containing a Class 4 part on the top storey, for the purpose of (1), the classification applying to the top storey must be—
when the Class 4 part occupies the whole of the top storey, the classification applicable to the next highest storey; or
when the Class 4 part occupies part of the top storey, the classification applicable to the adjacent part.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One C2D4.
Can't meet C2D4? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →