Deemed-to-Satisfy Provision · NCC 2025 Volume One
C2D8 Open spectator stands and indoor sports stadiums
Part C2 Fire resistance and stability · NCC 2019: C1.7
(1) An open spectator stand or indoor sports stadium may be of Type C construction and need not comply with the other provisions of this Part if it contains not more than one tier of seating, is of non-combustible construction, and has only changing rooms, sanitary facilities or the like below the tiered seating.
(2) In (1), one tier of seating means numerous rows of tiered seating incorporating cross-overs but within one viewing level.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One C2D8.
Can't meet C2D8? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →