C2D9 Lightweight construction
Part C2 Fire resistance and stability · NCC 2019: C1.8
(1) Lightweight construction must comply with Specification 6 if it is used in a wall system—
that is required to have an FRL; or
for a lift shaft, stair shaft or service shaft or an external wall bounding a public corridor including a non fire-isolated passageway or non fire-isolated ramp, in a spectator stand, sports stadium, cinema or theatre, railway station, bus station or airport terminal.
(2) If lightweight construction is used for the fire-resisting covering of a steel column or the like, and if—
the covering is not in continuous contact with the column, then the void must be filled solid, to a height of not less than 1.2 m above the floor to prevent indenting; and
the column is liable to be damaged from the movement of vehicles, materials or equipment, then the covering must be protected by steel or other suitable material.