C3D4 Large isolated buildings
Part C3 Compartmentation and separation
The size of a fire compartment in a building may exceed that specified in Table C3D3 where—
the building does not exceed 18 000 m2 in floor area nor exceed 108 000 m3 in volume, if—
the building is Class 7 or 8 and—
contains not more than 2 storeys; and
is provided with open space complying with C3D5(1) not less than 18 m wide around the building; or
the building is Class 5, 6, 7, 8 or 9 and is—
protected throughout with a sprinkler system complying with Specification 17; and
provided with a perimeter vehicular access complying with C3D5(2); or
the building is Class 5, 6, 7, 8 or 9 and exceeds 18 000 m2 in floor area or 108 000 m3 in volume, if it is—
protected throughout with a sprinkler system complying with Specification 17; and
provided with a perimeter vehicular access complying with C3D5(2); or
there is more than one building on the allotment and—
each building complies with (a) or (b); or
if the buildings are closer than 6 m to each other they are regarded as one building and collectively comply with (a) or (b).
Clauses referred to
- C3D3 General floor area and volume limitations
- C3D5 Requirements for open spaces and vehicular access