Deemed-to-Satisfy Provision · NCC 2025 Volume One

C4D11 Openings in fire-isolated lift shafts

Part C4 Protection of openings · NCC 2019: C3.10

Open C4D11 on NCC Online ↗

(1) Doorways — If a lift shaft is required to be fire-isolated, an entrance doorway to that shaft must be protected by –/60/– fire doors that—

comply with AS 1735.11; and

are set to remain closed except when discharging or receiving passengers, goods or vehicles.

(2) Lift indicator panels — A lift call panel, indicator panel or other panel in the wall of a fire-isolated lift shaft must be backed by construction having an FRL of not less than –/60/60 if it exceeds 35 000 mm2 in area.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One C4D11.
Can't meet C4D11? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →

Defined terms used