NCC 2025 Volume One
Part C4 Protection of openings
18 clauses · Open on NCC Online ↗
- C4D1 Deemed-to-Satisfy Provisions SAWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements C1P1 to C1P9 are satisfied by complying with— C2D2 to C2D15, C3D2 to C3D15…
- C4D2 Application of PartThe Deemed-to-Satisfy Provisions of this Part do not apply to the following: Control joints, weep holes and the like in external walls of masonry…
- C4D3 Protection of openings in external wallsSubject to (2), openings in an external wall, or openings in part of an external wall, where that external wall or external wall part is required to…
- Table C4D4 Distance between external walls and associated openings in different fire compartmentsAngle between walls | Minimum distance (m) 0° (walls opposite) | 6 more than 0° to 45° | 5 more than 45° to 90° | 4 more than 90° to 135° | 3 more…
- C4D4 Separation of external walls and associated openings in different fire compartmentsThe distance between parts of external walls and any openings within them in different fire compartments separated by a fire wall must not be less…
- C4D5 Acceptable methods of protectionWhere protection is required, doorways, windows and other openings must be protected as follows: Doorways— internal or external wall-wetting…
- C4D6 Doorways in fire wallsThe aggregate width of openings for doorways in a fire wall, which are not part of a horizontal exit, must not exceed ½ of the length of the fire…
- C4D7 Sliding fire doorsIf a doorway in a fire wall is fitted with a sliding fire door which is open when the building is in use— it must be held open with an…
- C4D8 Protection of doorways in horizontal exitsA doorway that is part of a horizontal exit must be protected by either— a single fire door that has an FRL of not less than that required by…
- C4D9 Openings in fire-isolated exitsDoorways that open to fire-isolated stairways, fire-isolated passageways or fire-isolated ramps, and are not doorways opening to a road or open…
- C4D10 Service penetrations in fire-isolated exitsFire-isolated exits must not be penetrated by any services other than— electrical wiring permitted by D3D8(6) to be installed within the exit; or…
- C4D11 Openings in fire-isolated lift shaftsDoorways — If a lift shaft is required to be fire-isolated, an entrance doorway to that shaft must be protected by –/60/– fire doors that— comply…
- C4D12 Bounding construction: Class 2 and 3 buildings and Class 4 parts NSWA doorway in a Class 2 or 3 building must be protected if it provides access from a sole-occupancy unit to— a public corridor, public lobby, or the…
- C4D13 Openings in floors and ceilings for servicesWhere a service passes through— a floor that is required to have an FRL with respect to integrity and insulation; or a ceiling required to have a…
- C4D14 Openings in shaftsIn a building of Type A construction, an opening in a wall providing access to a ventilating, pipe, garbage or other service shaft must be protected…
- C4D15 Openings for service installationsThe requirements of (2) apply where an electrical, electronic, plumbing, mechanical ventilation, air-conditioning or other service penetrates a…
- C4D16 Construction jointsConstruction joints, spaces and the like in and between building elements required to be fire-resisting with respect to integrity and insulation…
- C4D17 Columns protected with lightweight construction to achieve an FRLA column protected by lightweight construction to achieve an FRL which passes through a building element that is required to have an FRL or a…