Deemed-to-Satisfy Provision · NCC 2025 Volume One

C4D4 Separation of external walls and associated openings in different fire compartments

Part C4 Protection of openings · NCC 2019: C3.3

Open C4D4 on NCC Online ↗

The distance between parts of external walls and any openings within them in different fire compartments separated by a fire wall must not be less than that set out in Table C4D4, unless—

those parts of each wall have an FRL not less than 60/60/60; and

any openings are protected in accordance with C4D5.

Table C4D4 Distance between external walls and associated openings in different fire compartments

Angle between walls

Minimum distance (m)

0° (walls opposite)

6

more than 0° to 45°

5

more than 45° to 90°

4

more than 90° to 135°

3

more than 135° to less than 180°

2

180° or more

Nil

Tables

New in NCC 2025. No C4D4 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet C4D4? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →