Deemed-to-Satisfy Provision · NCC 2025 Volume One
C4D4 Separation of external walls and associated openings in different fire compartments
Part C4 Protection of openings · NCC 2019: C3.3
The distance between parts of external walls and any openings within them in different fire compartments separated by a fire wall must not be less than that set out in Table C4D4, unless—
those parts of each wall have an FRL not less than 60/60/60; and
any openings are protected in accordance with C4D5.
Table C4D4 Distance between external walls and associated openings in different fire compartments
Angle between walls
Minimum distance (m)
0° (walls opposite)
6
more than 0° to 45°
5
more than 45° to 90°
4
more than 90° to 135°
3
more than 135° to less than 180°
2
180° or more
Nil