C4D5 Acceptable methods of protection
Part C4 Protection of openings · NCC 2019: C3.4
(1) Where protection is required, doorways, windows and other openings must be protected as follows:
Doorways—
internal or external wall-wetting sprinklers as appropriate used with doors that are self-closing or automatic closing; or
–/60/30 fire doors that are self-closing or automatic closing.
Windows —
internal or external wall-wetting sprinklers as appropriate used with windows that are automatic closing or permanently fixed in the closed position; or
–/60/– fire windows that are automatic closing or permanently fixed in the closed position; or
–/60/– automatic closing fire shutters.
Other openings—
excluding voids — internal or external wall-wetting sprinklers, as appropriate; or
construction having an FRL not less than –/60/–.
(2) Fire doors, fire windows and fire shutters must comply with Specification 12.