Deemed-to-Satisfy Provision · NCC 2025 Volume One

C4D5 Acceptable methods of protection

Part C4 Protection of openings · NCC 2019: C3.4

Open C4D5 on NCC Online ↗

(1) Where protection is required, doorways, windows and other openings must be protected as follows:

Doorways—

internal or external wall-wetting sprinklers as appropriate used with doors that are self-closing or automatic closing; or

–/60/30 fire doors that are self-closing or automatic closing.

Windows —

internal or external wall-wetting sprinklers as appropriate used with windows that are automatic closing or permanently fixed in the closed position; or

–/60/– fire windows that are automatic closing or permanently fixed in the closed position; or

–/60/– automatic closing fire shutters.

Other openings—

excluding voids — internal or external wall-wetting sprinklers, as appropriate; or

construction having an FRL not less than –/60/–.

(2) Fire doors, fire windows and fire shutters must comply with Specification 12.

New in NCC 2025. No C4D5 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet C4D5? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →