Deemed-to-Satisfy Provision · NCC 2025 Volume One

C4D7 Sliding fire doors

Part C4 Protection of openings · NCC 2019: C3.6

Open C4D7 on NCC Online ↗

(1) If a doorway in a fire wall is fitted with a sliding fire door which is open when the building is in use—

it must be held open with an electromagnetic device, which when de-activated in accordance with (2) and (3), allows the door to be fully closed in not less than 20 seconds and not more than 30 seconds after release; and

in the event of power failure to the door — the door must fail safe in the closed position in accordance with (a); and

an audible warning device must be located near the doorway and a red flashing warning light of adequate intensity on each side of the doorway must be activated in accordance with (2) and (3); and

signs must be installed on each side of the doorway located directly over the opening stating, in capital letters not less than 50 mm high in a colour contrasting with the background:

WARNING — SLIDING FIRE DOOR

(2) The electromagnetic device required by (1)(a) must be de-activated and the warning system activated by heat or smoke detectors, as appropriate, installed in accordance with AS 1905.1 and the relevant provisions of AS 1670.1.

(3) Where any other required suitable fire alarm system, including a sprinkler system (other than a FPAA101D system) complying with Specification 17, is installed in the building, activation in either fire compartment separated by the fire wall must also de-activate the electromagnetic device and activate the warning system.

New in NCC 2025. No C4D7 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet C4D7? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →

Defined terms used