C4D8 Protection of doorways in horizontal exits
Part C4 Protection of openings · NCC 2019: C3.7
(1) A doorway that is part of a horizontal exit must be protected by either—
a single fire door that has an FRL of not less than that required by Specification 5 for the fire wall except that the door must have an insulation level of at least 30; or
in a Class 7 or 8 building — 2 fire doors, one on each side of the doorway, each with an FRL of not less than ½ that required by Specification 5 for the fire wall except that each door must have an insulation level of at least 30.
(2) Each door required by (1) must be self-closing, or automatic -closing in accordance with the following:
The automatic -closing operation must be initiated by the activation of a smoke detector, or any other detector deemed suitable in accordance with AS 1670.1 if smoke detectors are unsuitable in the atmosphere, installed in accordance with the relevant provisions of AS 1670.1 and located on each side of the fire wall not more than 1.5 m horizontal distance from the opening.
Where any other required suitable fire alarm system, including a sprinkler system (other than a FPAA101D system) complying with Specification 17, is installed in the building, activation of the system in either fire compartment separated by the fire wall must also initiate the automatic -closing operation.