Deemed-to-Satisfy Provision · NCC 2025 Volume One

D2D4 When fire-isolated stairways and ramps are required

Part D2 Provision for escape · NCC 2019: D1.3

Open D2D4 on NCC Online ↗

(1) Class 2 and 3 buildings — The following applies:

Subject to (b), every stairway or ramp serving as a required exit must be fire-isolated unless it connects, passes through or passes by not more than—

3 consecutive storeys in a Class 2 building; or

2 consecutive storeys in a Class 3 building.

Notwithstanding (a), one extra storey of any classification may be included if—

it is only for the accommodation of motor vehicles or for other ancillary purposes; or

the building has a sprinkler system (other than a FPAA101D system) complying with Specification 17 installed throughout; or

the required exit does not provide access to or egress for, and is separated from, the extra storey by construction having—

an FRL of –/60/60, if non-load bearing; and

an FRL of 90/90/90, if load bearing; and

no opening that could permit the passage of fire or smoke.

(2) Class 5, 6, 7, 8 or 9 buildings — Every stairway or ramp serving as a required exit must be fire-isolated unless—

in a Class 9a health-care building — it connects, or passes through or passes by not more than 2 consecutive storeys in areas other than patient care areas; or

it is part of an open spectator stand; or

in any other case, except in a Class 9b early childhood centre or a Class 9c building, it connects, passes through or passes by not more than 2 consecutive storeys and one extra storey of any classification may be included if—

the building has a sprinkler system (other than a FPAA101D system) complying with Specification 17 installed throughout; or

the required exit does not provide access to or egress for, and is separated from, the extra storey by construction having—

an FRL of –/60/60, if non-load bearing; and

an FRL of 90/90/90 for Type A construction or 60/60/60 for Type B or C construction, if load bearing; and

no opening that could permit the passage of fire or smoke.

Exemptions

D2D4(2) does not apply to—

a Class 9b early childhood centre wholly within a storey that provides direct egress to a road or open space; or

a Class 9b early childhood centre with a rise in storeys of not more than 2, where the Class 9b early childhood centre is the only use in that building.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One D2D4.
Can't meet D2D4? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P10, D1P9. Start a Performance Solution →

Defined terms used