Deemed-to-Satisfy Provision · NCC 2025 Volume One

D2D3 Number of exits required

Part D2 Provision for escape · NCC 2019: D1.2

Open D2D3 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) All buildings — Every building must have at least one exit from each storey.

(2) Class 2 to 8 buildings —

In addition to any horizontal exit, not less than 2 exits must be provided from the following:

Each storey if the building has an effective height of more than 25 m.

A Class 2 or 3 building subject to C2D6.

The requirements of (a)(i) do not apply to a part of a storey that—

is provided with direct egress to a road or open space; and

satisfies D2D5 by the provision of 1 exit.

(3) Basements — In addition to any horizontal exit, not less than 2 exits must be provided from any storey if egress from that storey involves a vertical rise within the building of more than 1.5 m, unless—

the floor area of the storey is not more than 50 m²; and

the distance of travel from any point on the floor to a single exit is not more than 20 m.

(4) Class 9 buildings —

In addition to any horizontal exit, not less than 2 exits must be provided from the following:

Each storey if the building has a rise in storeys of more than 6 or an effective height of more than 25 m.

Any storey which includes a patient care area in a Class 9a health-care building.

Any storey that contains sleeping areas in a Class 9c building.

Any storey used as a Class 9b early childhood centre, or any Class 9b early childhood centre which forms part of a storey.

Each storey in a primary or secondary school with a rise in storeys of 2 or more.

Any storey or mezzanine that accommodates more than 50 persons, calculated under D2D18.

The requirements of (a) do not apply to a part of a storey that—

is a plant room, machinery room, storeroom, lift-machine room or the like; and

is provided with direct egress to a road, open space or a fire-isolated exit complying with D2D12(2); and

satisfies D2D5 by the provision of 1 exit.

(5) Exits from Class 9c buildings and patient care areas in Class 9a health-care buildings — In a Class 9a health-care building and a Class 9c building, at least one exit must be provided from every part of a storey which has been divided into fire compartments in accordance with C3D3 or C3D6.

(6) Exits in open spectator stands — In an open spectator stand containing more than one tier of seating, every tier must have not less than 2 stairways or ramps, each forming part of the path of travel to not less than 2 exits.

(7) Access to exits — Without passing through another sole-occupancy unit every occupant of a storey or part of a storey must have access to—

an exit; or

at least 2 exits if 2 or more exits are required.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One D2D3.
Can't meet D2D3? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P10, D1P9. Start a Performance Solution →

State and territory variations all clauses side by side →