D3D25 Swinging doors
Part D3 Construction of exits · NCC 2019: D2.20
(1) A swinging door in a required exit or forming part of a required exit —
must not encroach—
at any part of its swing by more than 500 mm on the required width (including any landings) of a required stairway, ramp or passageway if it is likely to impede the path of travel of the people already using the exit; and
when fully open, by more than 100 mm on the required width of the required exit; and
must swing in the direction of egress unless—
it serves a building or part with a floor area not more than 200 m2, it is the only required exit from the building or part and it is fitted with a device for holding it in the open position; or
it serves a sanitary compartment or airlock (in which case it may swing in either direction); and
must not otherwise impede the path or direction of egress.
(2) The measurement of encroachment referred to in (1)(a) in each case is to include door handles or other furniture or attachments to the door.