Deemed-to-Satisfy Provision · NCC 2025 Volume One

D3D26 Operation of latch

Part D3 Construction of exits · NCC 2019: D2.21

Open D3D26 on NCC Online ↗
Varied in NSW, VIC. Check the variation for your state.

(1) A door in a required exit, forming part of a required exit or in the path of travel to a required exit must be readily openable without a key from the side that faces a person seeking egress, by—

a single hand downward action on a single device which is located between 900 mm and 1.1 m from the floor and if serving an area required to be accessible by Part D4 —

be such that the hand of a person who cannot grip will not slip from the handle during the operation of the latch; and

have a clearance between the handle and the back plate or door face at the centre grip section of the handle of not less than 35 mm and not more than 45 mm; or

a single hand pushing action on a single device which is located between 900 mm and 1.2 m from the floor.

(2) Where the latch operation device referred to in (1)(b) is not located on the door leaf itself—

manual controls to power-operated doors must be at least 25 mm wide, proud of the surrounding surface and located—

not less than 500 mm from an internal corner; and

for a hinged door, between 1 m and 2 m from the door leaf in any position; and

for a sliding door, within 2 m of the doorway and clear of a surface mounted door in the open position; and

braille and tactile signage complying with S15C3 and S15C6 must identify the latch operation device.

(3) The requirements of (1) and (2) do not apply to a door that—

serves a vault, strong-room, sanitary compartment, or the like; or

serves only, or is within—

a sole-occupancy unit in a Class 2 building or a Class 4 part of a building; or

a sole-occupancy unit in a Class 3 building (other than an entry door to a sole-occupancy unit of a boarding house, guest house, hostel, lodging house or backpacker accommodation); or

a sole-occupancy unit with a floor area not more than 200 m2 in a Class 5, 6, 7 or 8 building; or

a space which is otherwise inaccessible to persons at all times when the door is locked; or

complies with (4) and serves—

Australian Government Security Zones 4 or 5; or

the secure parts of a bank, detention centre, mental health facility, early childhood centre or the like; or

is fitted with a fail-safe device which automatically unlocks the door upon the activation of any sprinkler system (other than a FPAA101D system) complying with Specification 17 or smoke, or any other detector system deemed suitable in accordance with AS 1670.1 installed throughout the building, and is readily openable when unlocked; or

is in a Class 9a or 9c building and—

is one leaf of a two-leaf door complying with D2D9(a) or D2D9(d) provided that it is not held closed by a locking mechanism and is readily openable; and

the door is not required to be a fire door or smoke door.

(4) A door referred to in (3)(c) must be able to be immediately unlocked—

by operating a fail-safe control switch, not contained within a protective enclosure, to actuate a device to unlock the door; or

by hand by a person or persons, specifically nominated by the owner, properly instructed as to the duties and responsibilities involved and available at all times when the building is lawfully occupied so that persons in the building or part may immediately escape if there is a fire.

(5) The requirements of (1) and (2) do not apply in a Class 9b building (other than a school, an early childhood centre or a building used for religious purposes) to a door in a required exit, forming part of a required exit or in the path of travel to a required exit serving a storey or room accommodating more than 100 persons, determined in accordance with D2D18, in which case it must be readily openable—

without a key from the side that faces a person seeking egress; and

by a single hand pushing action on a single device such as a panic bar located between 900 mm and 1.2 m from the floor; and

where a two-leaf door is fitted, the provisions of (a) and (b) need only apply to one door leaf if the appropriate requirements of D2D9 are satisfied by the opening of that one leaf.

New in NCC 2025. No D3D26 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet D3D26? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P10, D1P9. Start a Performance Solution →

State and territory variations all clauses side by side →