E1D14 Portable fire extinguishers
Part E1 Fire fighting equipment · NCC 2019: E1.6 and Table E1.6
(1) Portable fire extinguishers must be—
provided as listed in (3) and (4); and
for a Class 2, 3 or 5 building or Class 4 part of a building, provided—
to serve the whole Class 2, 3 or 5 building or Class 4 part of a building where one or more internal fire hydrants are installed; or
where internal fire hydrants are not installed, to serve any fire compartment with a floor area greater than 500 m2, and for the purposes of this clause, a sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building is considered to be a fire compartment; and
subject to (2), selected, located and distributed in accordance with Sections 1, 2, 3 and 4 of AS 2444.
(2) Portable fire extinguishers provided in a Class 2 or 3 building or Class 4 part of a building must be—
an ABE type fire extinguisher; and
a minimum size of 2.5 kg; and
distributed outside a sole-occupancy unit —
to serve only the storey at which they are located; and
so that the travel distance from the entrance doorway of any sole-occupancy unit to the nearest fire extinguisher is not more than 10 m.
(3) In Class 2 to 9 buildings (except within sole-occupancy units of a Class 9c building), portable fire extinguishers must be provided as follows:
To cover Class AE or E fire risks associated with emergency services switchboards.
To cover Class F fire risks involving cooking oils and fats in kitchens.
To cover Class B fire risks in locations where flammable liquids in excess of 50 litres are stored or used (not including that held in fuel tanks of vehicles).
To cover Class A fire risks in normally occupied fire compartments less than 500 m2 not provided with fire hose reels (excluding open-deck carparks).
To cover Class A fire risks in classrooms and associated corridors in primary and secondary schools not provided with fire hose reels.
To cover Class A fire risks associated with a Class 2, 3 or 5 building or Class 4 part of a building.
(4) In addition to the requirements of (3), portable fire extinguishers must be provided to cover Class A and E fire risks in the following occupancies in buildings, or parts of a building:
A Class 9a health-care building, including a Class 9a building used as a residential care building.
Class 3 parts of detention and correctional occupancies.
Class 3 accommodation for children, aged persons and people with disabilities, including a Class 3 building used as a residential care building.
A Class 9c building.
(5) For the purposes of (3) and (4):
Fire risks are defined in accordance with AS 2444.
An emergency services switchboard is one which sustains emergency equipment operating in the emergency mode.
Additional extinguishers may be required to cover fire risks in relation to special hazards provided for in E1D17.
The fire risks in a Class 2 or 3 building or Class 4 part of a building must include risks within any sole-occupancy units, however portable fire extinguishers are not required to be located within a sole-occupancy unit unless the sole-occupancy unit has a floor area greater than 500 m2.
(6) For the purposes of (4), where applicable, a Class E fire extinguisher need only be located at each nurses’ station, supervisors’ station or the like.