Deemed-to-Satisfy Provision · NCC 2025 Volume One

E1D16 Fire precautions during construction

Part E1 Fire fighting equipment · NCC 2019: E1.9

Open E1D16 on NCC Online ↗

In a building under construction—

not less than one fire extinguisher to suit Class A, B and C fires and electrical fires must be provided at all times on each storey adjacent to each required exit or temporary stairway or exit; and

after the building has reached an effective height of 12 m—

the required fire hydrants and fire hose reels must be operational in at least every storey that is covered by the roof or the floor structure above, except the 2 uppermost storeys; and

any required booster connections must be installed.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One E1D16.
Can't meet E1D16? A Performance Solution must meet the Performance Requirements it satisfies: E1P1, E1P2, E1P3, E1P4, E1P5, E1P6. Start a Performance Solution →

Defined terms used