Deemed-to-Satisfy Provision · NCC 2025 Volume One

E2D14 Class 6 buildings – in fire compartments more than 2000 m2: Class 6 building (not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit)

Part E2 Smoke hazard management · NCC 2019: Table E2.2b

Open E2D14 on NCC Online ↗

(1) This clause applies to a Class 6 building not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit, except for—

a Class 6 sole-occupancy unit that—

has a floor area of not more than 2000 m2; and

is single storey with a main public entrance opening to a road or open space; and

is separated from other parts of the fire compartment by construction, including openings, penetrations and junctions with other building elements, that prevents the free passage of smoke; and

parts of any other classification that are smoke separated from a Class 6 part by construction complying with (a)(iii).

(2) Where the floor area of a Class 6 part of a fire compartment referred to in (1) is more than 2000 m2, the fire compartment must be provided with—

an automatic smoke exhaust system complying with Specification 21; or

if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or

if the floor area of the fire compartment is not more than 3500 m2 and the building—

is single storey, an automatic smoke detection and alarm system complying with Specification 20; or

has a rise in storeys of not more than 2, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One E2D14.
Can't meet E2D14? A Performance Solution must meet the Performance Requirements it satisfies: E2P1, E2P2. Start a Performance Solution →