Deemed-to-Satisfy Provision · NCC 2025 Volume One

E2D13 Basements (other than Class 7a buildings)

Part E2 Smoke hazard management · NCC 2019: Table E2.2a

Open E2D13 on NCC Online ↗

(1) A basement, other than a Class 7a basement, not counted in the rise in storeys in accordance with C2D3, must—

comply with measures in accordance with this Part applicable to the building generally; and

where the basement has a total floor area of more than 2000 m2, be provided with—

if not more than 2 below ground storeys —

a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the basement has more than one fire compartment; or

an automatic smoke detection and alarm system complying with Specification 20; or

a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; or

if more than 2 below ground storeys, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.

(2) For the purposes of (1), ‘vertically separated fire compartments ’ are fire compartments above and below each other, and not fire compartments within the same storey.

Notes

Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.

Basements with more than 3 below ground storeys or containing Class 6 or 9b occupancies with a large number of occupants may require special consideration in accordance with E2D21.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One E2D13.
Can't meet E2D13? A Performance Solution must meet the Performance Requirements it satisfies: E2P1, E2P2. Start a Performance Solution →