E2D13 Basements (other than Class 7a buildings)
Part E2 Smoke hazard management · NCC 2019: Table E2.2a
(1) A basement, other than a Class 7a basement, not counted in the rise in storeys in accordance with C2D3, must—
comply with measures in accordance with this Part applicable to the building generally; and
where the basement has a total floor area of more than 2000 m2, be provided with—
if not more than 2 below ground storeys —
a zone pressurisation system between vertically separated fire compartments in accordance with AS 1668.1, if the basement has more than one fire compartment; or
an automatic smoke detection and alarm system complying with Specification 20; or
a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; or
if more than 2 below ground storeys, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
(2) For the purposes of (1), ‘vertically separated fire compartments ’ are fire compartments above and below each other, and not fire compartments within the same storey.
Notes
Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.
Basements with more than 3 below ground storeys or containing Class 6 or 9b occupancies with a large number of occupants may require special consideration in accordance with E2D21.
Clauses referred to
- C2D3 Calculation of rise in storeys
- E2D14 Class 6 buildings – in fire compartments more than 2000 m2: Class 6 building (not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit)
- E2D20 Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
- E2D21 Provision for special hazards