E2D15 Class 6 buildings – in fire compartments more than 2000 m2: Class 6 building (containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit)
Part E2 Smoke hazard management · NCC 2019: Table E2.2b
(1) This clause applies to a Class 6 building containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit, except for—
a Class 6 sole-occupancy unit that—
opens onto the enclosed common walkway or mall if the Class 6 sole-occupancy unit has a floor area of not more than 1000 m2; or
does not open onto the enclosed common walkway or mall if the Class 6 sole-occupancy unit —
has a floor area of not more than 2000 m2; and
is single storey with a main entrance opening to a road or open space; and
is separated from other parts of the fire compartment by construction, including openings, penetrations and junctions with other building elements, that prevents the free passage of smoke; and
parts of any other classification that are smoke separated from a Class 6 part by construction complying with (a)(ii)(C).
(2) Where the floor area of a Class 6 part of a fire compartment referred to in (1) is more than 2000 m2, the fire compartment, including the enclosed common walkway or mall, must be provided with—
an automatic smoke exhaust system complying with Specification 21; or
if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or
if the floor area of the fire compartment is not more than 3500 m2 and the building has a rise in storeys of not more than 2, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
Notes
A fire compartment having a floor area of more than 3500 m2 in a Class 6 building requires a sprinkler system under E1D4.