E2D16 Class 9b – assembly buildings: nightclubs, discotheques and the like
Part E2 Smoke hazard management · NCC 2019: NSW Table E2.2b, Table E2.2b
A Class 9b assembly building which is a nightclub, discotheque or the like must be provided with—
automatic shutdown of any air-handling system (other than miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
smoke detectors installed complying with S20C6; and
any other installed fire detection and alarm system, including a sprinkler system complying with Specification 17; and
at least one of the following:
An automatic smoke exhaust system complying with Specification 21.
If the building is single storey, automatic smoke-and-heat vents complying with Specification 22.
A sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 with quick response sprinkler heads.