Deemed-to-Satisfy Provision · NCC 2025 Volume One

E4D5 Exit signs

Part E4 Visibility in an emergency, exit signs and warning systems · NCC 2019: SA E4.5(e), E4.5

Open E4D5 on NCC Online ↗

An exit sign must be clearly visible to persons approaching the exit, and must be installed on, above or adjacent to each—

door providing direct egress from a storey to—

an enclosed stairway, passageway or ramp serving as a required exit; and

an external stairway, passageway or ramp serving as a required exit; and

an external access balcony leading to a required exit; and

door from an enclosed stairway, passageway or ramp at every level of discharge to a road or open space; and

horizontal exit; and

door serving as, or forming part of, a required exit in a storey required to be provided with emergency lighting in accordance with E4D2.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One E4D5.
Can't meet E4D5? A Performance Solution must meet the Performance Requirements it satisfies: E4P1, E4P2, E4P3. Start a Performance Solution →