Deemed-to-Satisfy Provision · NCC 2025 Volume One

F1D14 Glazed assemblies

Part F1 Water management

Open F1D14 on NCC Online ↗

(1) Subject to (2) and (3), the following glazed assemblies in an external wall, must comply with AS 2047 requirements for resistance to water penetration:

Windows.

Sliding and swinging glazed doors with a frame, including french and bi-fold doors with a frame.

Adjustable louvres.

Shopfronts.

Window walls with one piece framing.

(2) The following buildings need not comply with (1):

A private garage, tool shed, sanitary compartment, or the like, forming part of a building used for other purposes, except where the construction of the garage, tool shed, sanitary compartment or the like contributes to the weatherproofing of the other part of the building.

An open spectator stand or open-deck carpark.

(3) The following glazed assemblies need not comply with (1):

All glazed assemblies not in an external wall.

Revolving doors.

Fixed louvres.

Skylights, roof lights and windows in other than the vertical plane.

Sliding and swinging glazed doors without a frame.

Windows constructed on site and architectural one-off windows, which are not design tested in accordance with AS 2047.

Second-hand windows, re-used windows and recycled windows.

Heritage windows.

New in NCC 2025. No F1D14 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet F1D14? A Performance Solution must meet the Performance Requirements it satisfies: F1P1. Start a Performance Solution →