Deemed-to-Satisfy Provision · NCC 2025 Volume One

F1D15 Wall cladding

Part F1 Water management

Open F1D15 on NCC Online ↗

(1) External wall cladding must comply with one or a combination of the following:

Masonry, including masonry veneer, unreinforced and reinforced masonry: AS 3700.

Autoclaved aerated concrete: AS 5146.3.

Metal wall cladding: AS 1562.1.

(2) The following buildings need not comply with (1):

A private garage, tool shed, sanitary compartment, or the like, forming part of a building used for other purposes, except where the construction of the garage, tool shed, sanitary compartment or the like contributes to the weatherproofing of another part of the building that is required to be weatherproofed.

An open spectator stand or open deck carpark.

New in NCC 2025. No F1D15 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet F1D15? A Performance Solution must meet the Performance Requirements it satisfies: F1P1. Start a Performance Solution →