Deemed-to-Satisfy Provision · NCC 2025 Volume One

F1D6 Exposed joints

Part F1 Water management · NCC 2019: F1.9

Open F1D6 on NCC Online ↗

Exposed joints in the drainage surface on a roof, balcony, podium or similar horizontal surface part of a building must—

be located on the ridge line or high point of the structural substrate; and

be protected in accordance with Section 2.9 of AS 4654.2; and

not be located beneath or run through a planter box, water feature or similar part of the building.

Notes

For the purposes of F1D6, an exposed joint is a construction joint, control joint, expansion joint, contraction joint or movement joint and includes an exposed joint which is directly below a drainage surface.

Changed since NCC 2022. See NCC 2022 Volume One F1D6, or show what changed.

(1) Except for a building covered by (3), moisture from the ground must be prevented from reaching — the lowest floor timbers and the walls above the lowest floor joists; and the walls above the damp-proof course; and the underside of a suspended floor constructed of a material other than timber, and the supporting beams or girders. (2) Where a damp-proof course is provided, it must consist of — a material that complies with AS/NZS 2904; or impervious sheet material in accordance with AS 3660.1. (3) The following buildings need not comply with (1): A Class 7 or 8 building where Exposed joints in the particular case there is no necessity for compliance. A garage, tool shed, sanitary compartment, drainage surface on a roof, balcony, podium or the like, forming similar horizontal surface part of a building used for other purposes. An open spectator stand must — be located on the ridge line or open-deck carpark. high point of the structural substrate; and be protected in accordance with Section 2.9 of AS 4654.2; and not be located beneath or run through a planter box, water feature or similar part of the building. Notes For the purposes of F1D6, an exposed joint is a construction joint, control joint, expansion joint, contraction joint or movement joint and includes an exposed joint which is directly below a drainage surface.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet F1D6? A Performance Solution must meet the Performance Requirements it satisfies: F1P1. Start a Performance Solution →