F1V1 Weatherproofing
(1) Compliance with F1P1 for weatherproofing of an external wall is verified when—
a prototype passes the procedure described in (2); and
the external wall —
has a risk score of 20 or less, when the sum of all risk factor scores are determined in accordance with Table F1V1a; and
includes only windows that comply with AS 2047.
(2) The test procedure referred to in (1)(a) must be as follows:
The test specimen is in accordance with the requirements of (3).
The test procedure is in accordance with the requirements of (4) or (5) as applicable.
The test specimen does not fail the criteria in (6).
The test is recorded in accordance with the requirements of (7).
(3) Test specimen: The test specimen must be a minimum of 2.4 m high and 2.4 m wide and incorporate—
representative samples of openings and joints, including—
vertical and horizontal control joints; and
wall junctions; and
windows or doors; and
electrical boxes; and
balcony drainage and parapet flashings; and
footer and header termination systems; and
for a cavity wall —
a transparent material for a proportion of the internal wall lining (to provide an unobstructed view of the external wall cladding) with sufficient structural capability and similar air tightness to resist the applied wind pressures; and
a 15 mm diameter hole in the internal wall lining below a window.
(4) The test procedure for a direct fix cladding wall or unique wall must be as follows:
Apply 100% positive and negative serviceability wind pressures to the external face of the test specimen for a period of not less than 1 minute each.
Apply static pressure of either 300 Pa or 30% serviceability wind pressure, whichever is higher, in accordance with the water penetration test procedure at clause 8.5.2 of AS/NZS 4284.
Apply cyclic pressure in accordance with—
the three stages of Table F1V1b; and
the water penetration test procedure at clause 8.6.2 of AS/NZS 4284.
(5) The test procedure for a cavity wall must be as follows:
Apply 100% positive and negative serviceability wind pressures to the external face of the test specimen for a period of not less than 1 minute each.
Apply static pressure of either 300 Pa or 30% serviceability wind pressure, whichever is higher, in accordance with the water penetration test procedure at clause 8.5.2 of AS/NZS 4284.
Apply cyclic pressure in accordance with—
stage 3 of Table F1V1b; and
the water penetration test procedure at clause 8.6.2 of AS/NZS 4284.
To simulate the failure of the primary weather-defence or sealing, the following procedure must be applied to the test specimen:
Insert 6 mm diameter holes through the external face of the cavity wall in all places specified below:
Wall/window or wall/door junctions at ¾ height.
Immediately above the head flashing.
Through external sealing of the horizontal and vertical joints.
Above any other penetration detail not covered by (A) to (C).
Repeat the static and cyclic pressure tests of (b) and (c).
Within 30 minutes of the completion of (ii), remove the internal lining of the cavity wall and check for compliance with (6).
With the internal lining removed, apply a final static pressure test at 50 Pa for a period of 15 minutes and check for compliance with (6).
(6) Compliance is determined as follows:
A direct fix cladding wall and unique wall are verified for compliance with F1P1 if there is no presence of water on the inside surface of the facade.
A cavity wall is verified for compliance with F1P1 if there is no presence of water on the removed surface of the cavity, except that during the simulation of the failure of the primary weather-defence or sealing, water may—
transfer to the removed surface of the cavity due to the introduced defects (6 mm holes); and
contact, but not pool on, battens and other cavity surfaces.
(7) The test report must include the following information:
Name and address of the person supervising the test.
Test report number.
Date of the test.
Cladding manufacturer’s name and address.
Construction details of the test specimen, including a description, and drawings and details of the components, showing modifications, if any.
Test sequence with the pressures used in all tests.
For each of the static and cyclic pressure tests, full details of all leakages, including position, extent and timing.
Table F1V1a Risk factors and scores
Risk factor
Category
Risk severity
Score
Wind region
Region A0-5 (AS/NZS 1170.2)
Low to medium
0
Region B1-2 (AS/NZS 1170.2)
Region C (AS/NZS 1170.2)
High
1
Region D (AS/NZS 1170.2)
Very high
2
Number of storeys
One storey
Low
0
Two storeys in part
Medium
1
Two storeys
High
2
More than two storeys
Very high
4
Roof/wall junctions
Roof-to-wall junctions fully protected
Low
0
Roof-to-wall junctions partially exposed
Medium
1
Roof-to-wall junctions fully exposed
High
3
Roof elements finishing within the boundaries formed by the external walls
Very high
5
Eaves width
More than 600 mm for single storey
Low
0
451-600 mm for single storey
Medium
1
More than 600 mm for two storey
101-450 mm for single storey
High
2
451-600 mm for two storey
More than 600 mm for above two storey
0-100 mm for single storey
Very high
5
0-450 mm for two storey
Less than 600 mm for above two storey
Envelope complexity
Simple shape with single cladding type
Low
0
Complex shape with not more than two cladding types
Medium
1
Complex shape with more than two cladding types
High
3
As for high risk but with fully exposed roof-to-wall junctions
Very high
6
Decks, porches and balconies
None
Low
0
Timber slat deck or porch at ground level
Fully covered in plan view by roof
Medium
2
Timber slat deck attached at first or second floor level
Balcony exposed in plan view at first floor level
High
4
Balcony cantilevered at first floor level
Balcony exposed in plan view at second floor level or above
Very high
6
Balcony cantilevered at second floor level or above
Table Notes
Eaves width is measured horizontally from the external face of any wall cladding to the outer edge of any overhang, including fascia and external gutters.
Barriers to prevent falling and parapets are considered as 0 mm eaves.
Table F1V1b Cyclic pressure
Stage number
Serviceability wind pressure (%)
Min
Max
1
15
30
2
20
40
3
30
60