NCC 2025 Volume One
Part F6 Light and ventilation
26 clauses · Open on NCC Online ↗
- F6O1 ObjectiveThe Objective of this Part is to— safeguard occupants from injury, illness or loss of amenity due to— isolation from natural light; and lack of…
- F6F1 Natural lightA space within a building used by occupants is to be provided with openings to admit natural light consistent with its function or use.
- F6F2 Artificial lightA space within a building used by occupants is to be provided with artificial lighting consistent with its function or use which, when activated in…
- F6F3 VentilationA space used by occupants within a building is to be provided with adequate ventilation consistent with its function or use.
- F6P1 Natural lightingSufficient openings must be provided and distributed in a building, appropriate to the function or use of that part of the building so that natural…
- F6P2 Artificial lightingArtificial lighting must be installed to provide an illuminance of not less than 20 lux appropriate to the function or use of the building to enable…
- F6P3 Outdoor air supplyA space in a building used by occupants must be provided with means of ventilation with outdoor air which will maintain adequate air quality.
- F6P4 Mechanical ventilation to control odours and contaminantsA mechanical air-handling system installed in a building must control— the circulation of objectionable odours; and the accumulation of harmful…
- F6P5 Disposal of contaminated airContaminated air must be disposed of in a manner which does not unduly create a nuisance or hazard to people in the building or other property.
- Table F6V1 Maximum contaminant limits for acceptable indoor air qualityPollutant | Averaging time | Maximum air quality value Carbon dioxide, CO2 | 8 hours | 850 ppm Note 1 Carbon monoxide, CO | 15 minutes | 90 ppm…
- F6V1 Verification of suitable indoor air qualityFor a Class 2, 3, 5, 6, 9b or 9c building or Class 4 part of a building, compliance with F6P3 and F6P4(a) is verified when it is determined that the…
- Table F6V2 Maximum carbon monoxide exposure for carparksConcentration (ppm) | Total exposure duration per day 100 | Not to be exceeded 90 | 15 minutes 60 | 1 hour 30 | 8 hours Table Notes Various…
- F6V2 Verification of suitable indoor air quality for carparksFor a Class 7a building, compliance with F6P3 and F6P4(a) is verified when it is determined that the building is provided with sufficient…
- F6V3 Verification of suitable provision of natural lightCompliance with F6P1 is verified for the provision of natural light when the average daylight factor for each window is determined in accordance…
- F6D1 Deemed-to-Satisfy Provisions SAWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements F6P1 to F6P5 are satisfied by complying with— F6D2 to F6D12; and for a…
- F6D2 Provision of natural lightNatural light must be provided in: A Class 2 building and a Class 4 part of a building — to all habitable rooms. A Class 3 building — to all…
- F6D3 Methods and extent of natural lightRequired natural light must be provided by— windows, excluding roof lights, that— have an aggregate light transmitting area measured exclusive of…
- F6D4 Natural light borrowed from adjoining roomNatural light to a room in a Class 2 building or Class 4 part of a building or in a sole-occupancy unit of a Class 3 building, may come through one…
- F6D5 Artificial lightingArtificial lighting must be provided— in required stairways, passageways, and ramps; and if natural light of a standard equivalent to that required…
- F6D6 Ventilation NSWA habitable room, office, shop, factory, workroom, sanitary compartment, bathroom, shower room, laundry and any other room or space occupied by a…
- F6D7 Natural ventilationNatural ventilation provided in accordance with F6D6(a) must consist of openings, windows, doors or other devices which can be opened— with a…
- F6D8 Ventilation borrowed from adjoining roomNatural ventilation to a room may come through a window, opening, door or other device from an adjoining room (including an enclosed verandah) if…
- F6D9 Restriction on location of sanitary compartmentsA sanitary compartment must not open directly into— a kitchen or pantry; or a public dining room or restaurant; or a dormitory in a Class 3…
- F6D10 AirlocksIf a sanitary compartment is prohibited under F6D9 from opening directly to another room— in a sole-occupancy unit in a Class 2 or 3 building or…
- F6D11 CarparksEvery storey of a carpark, except an open-deck carpark, must have— a system of mechanical ventilation complying with AS 1668.2; or a system of…
- F6D12 Kitchen local exhaust ventilationA kitchen must be provided with a kitchen exhaust hood system complying with AS 1668.1 and AS 1668.2 where— any cooking apparatus has— a total…