F7V2 Sound transmission through walls [F7P2(a)]
Part F7 Sound transmission and insulation · NCC 2019: FV5.2
Compliance with F7P2(a) to avoid the transmission of airborne sound through walls is verified when it is measured in-situ that—
a wall separating sole-occupancy units has a weighted standardised level difference with spectrum adaptation term (DnT,w + Ctr) not less than 45 when determined under AS ISO 717.1; or
a wall separating a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby, or the like, or parts of a different classification, has a weighted standardised level difference (DnT,w) not less than 45 when determined under AS ISO 717.1; or
any door assembly located in a wall that separates a sole-occupancy unit from a stairway, public corridor, public lobby, or the like, has a weighted standardised level difference (DnT,w) not less than 25 when determined under AS ISO 717.1.
Changed since NCC 2022 (minor wording). See NCC 2022 Volume One F7V2, or show what changed.
Compliance with F7P2(a) to avoid the transmission of airborne sound … (DnT,w + Ctr) not less than 45 when determined under AS/NZS AS ISO 717.1; or a wall separating a sole-occupancy unit from … level difference (DnT,w) not less than 45 when determined under AS/NZS AS ISO 717.1; or any door assembly located in a wall … level difference (DnT,w) not less than 25 when determined under AS/NZS AS ISO 717.1.